FLN36 high/medium voltage SF6 load break switch, with a rated voltage of 12kv, 24kv or 36kv, can response and protect power system when there is an error. The switch can be either manual operation or electrical operation, and earthing function is optional. Switch fuse combination can protect the whole system.
Compact size, easy installation and free of maintainence make the switch suitable for wide applications, especially for ring main unit. It also can work with vacuum circuit breaker to make a switchgear combination for excellent performance with favorable cost.
No. |
ltems |
Unit |
Value | |||||
FLN36-40.5 | FLRN36-40.5 | |||||||
1 | Rated voltage | KV | 40.5 | |||||
2 | Rated frequency | Hz | 50/60 | |||||
3 | Rated current | A | 630 | 1250 | ||||
4 | Rated insulation level |
1 min power frequency withstand voltage |
phase to phase | KV | 85 | |||
phase to earth | KV | 85 | ||||||
fracture | 110 | |||||||
Lightning impulse ithstand voltage voltage(peak) |
phase-to-phase | 85 | ||||||
phase to earth | 185 | |||||||
fracture | 215 | |||||||
5 | Auxiliary circuit 1 min power frequency | V | 2000 | |||||
6 | Rated thermal stability current /duration (3s/2s) | main switch | KA | 20/3 | ||||
earthing switch | 20/2 | |||||||
7 | Rated short-circuit making current | KA | 50 | 125 | ||||
8 | Rated closed circuit breaking current | A | 630 | |||||
9 | Rated active load breaking current | A | 630 | |||||
10 | Rated cable charging breaking current | A | 10 | |||||
12 | Rated transfer current | A | -- | 1700 | ||||
13 | Expected short-circuit breaking current | KA | -- | 50 | ||||
14 | Mechanical life | times | 2000 | |||||
15 | SF6 gas rated inflation pressure(20ºC gauge pressure) | MPa | 0.06 | |||||
16 | SF6 gas highest pressure (20ºC gauge pressure) | MPa | 0.07 | |||||
17 | Annual air leakage rate | %/Y | 0.5 | |||||
18 | Synchronicity of opening and closing | ms | ≤3 | |||||
17 | circuit resistance | μΩ | ≤100 | |||||
Fuse Rated Parameters | ||||||||
No. |
Rated Voltage (KV) |
Fuse Rated Current (A) |
Fuse Link Rated Curent(A) |
Rated Breaking Current (KA) |
||||
1 | 40.5 | 40 | 6.3,10,16,20,25,31.5,40 | 40 | ||||
2 | 100 | 506,380,100 | 40 | |||||
3 | 125 | 125 | 50 |