Product Description
Upper limit +80 'C , Lower limit:. -25 'C, The average temperature measured within 24 hours shall not exceed 35 "C
b) Altitude: ≤ 3,000 meters.
c)Installation Environment
The surrounding air should not be significantly contaminated by dust, smoke, corrosive/flammable gases, vapors, or salt mist
d) Relative Humidity:
Daily average ≤ 95%, Monthly average ≤ 90%
e) Electromagnetic Interference:
The induced electromagnetic interference amplitude in the secondary system shall not exceed 1.6 kV.
f) Vibration Conditions:
No frequent severe vibrations; seismic intensity shall not exceed 8 degrees
g) Application Site: Indoor use only.
Note: lf the environmental conditions exceed the specified range, the user must consult with the manufacturer to confirm feasilbilty
-
Product Parameters
Item |
Unit |
Circuit Breaker Unit |
Load Switch Unit |
Switch-fuse Combinations Unit |
Rated Voltage |
kV |
12 |
12 |
12 |
Rated Frequency |
Hz |
50 |
50 |
50 |
Rated Current |
A |
630/1250 |
630/1250 |
Dependent on Fuse Current Rating |
Rated Insulation Level |
|
|
|
|
- Power Frequency Withstand Voltage (Phase-to-Phase / Phase-to-Ground) |
kV |
42 |
42 |
42 |
- Power Frequency Withstand Voltage (Vacuum Interrupter / Isolation Gap) |
kV |
48 |
48 |
48 |
- Power Frequency Withstand Voltage (Control and Auxiliary Circuits) |
kV |
2 |
2 |
2 |
- Lightning Impulse Withstand Voltage (Phase-to-Phase / Phase-to-Ground) |
kV |
75 |
75 |
75 |
- Lightning Impulse Withstand Voltage (Vacuum Interrupter / Isolation Gap) |
kV |
85 |
85 |
85 |
Rated Short-Time Withstand Current |
kA |
20 (25) /4S |
20 (25) /4S |
- |
Rated Peak Withstand Current |
kA |
50 (63) |
50 (63) |
- |
Rated Short-Circuit Making Current |
kA |
50 (63) |
50 (63) |
Limited by High-Voltage Fuse |
Rated Short-Circuit Breaking Current |
kA |
20 (25) |
20 (25) |
Limited by High-Voltage Fuse |
Rated Transfer Current |
A |
- |
- |
1700 |
Rated Active Load Breaking Current |
A |
- |
- |
- |
Rated Closed-Loop Breaking Current |
A |
630 |
630 |
- |
Internal Arc Fault Test (AFLR Class) |
kA/S |
20 (25) /0.5S |
20 (25) /0.5S |
- |
Partial Discharge (at 1.2Ur) |
PC |
≤10 |
≤10 |
- |
Ingress Protection (IP) Rating (Cabinet) |
μΩ |
IP4X |
IP4X |
IP4X |
Main Circuit Resistance |
μΩ |
≤120 |
≤120 |
- |
Mechanical Endurance |
|
|
|
|
- Circuit Breaker / Load Switch |
Times |
10000 |
10000 |
10000 |
- Disconnector / Grounding Switch |
Times |
3000 |
3000 |
3000 |
Installation Instructions

Company Profile




FAQ
Q 1. Are you factory?
A.YES, Welcome to visit our company and factory.
Q 2. How's the delivery time?
A. Usually it will take about 7-30 days for MOQ
Q 3.Can you design customer's packing?
A.YES.We can customized the package for you.
Q 4.Do you have abilityfor OEM/0DM cooperation?
A.OEM/ODM cooperation is welcomed. And we have full experience about them.
Q 5.We wants to know month capacity.
A. lt depends on which model. Generally, month capacity can reach near 100,000pcs.