Customization: | Available |
---|---|
Installation: | Indoor High-Voltage |
Grounding: | Single Ground |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. | Items | Unit | Value | |||
FLN36-12 | FLRN36-12 | |||||
1 | Rated voltage | kV | 12 | |||
2 | Rated frequency | Hz | 50/60 | |||
3 | Rated current | A | 630 | 1250 | ||
4 | Rated insulation level | 1 min power frequency withstand voltage | phase-to-phase | kV | 42 | |
phase-to-earth | 42 | |||||
fracture | 48 | |||||
Lightning impulse withstand voltage voltage(peak) | phase-to-phase | 75 | ||||
phase to earth | 75 | |||||
fracture | 85 | |||||
5 | Auxiliary circuit 1 min power frequency | V | 2000 | |||
6 | Rated thermal stability current /duration (3s/2s) | main switch | kA | 20/3 | ||
earthing switch | 20/2 | |||||
7 | Rated short-circuit making current | KA | 50 | 125 | ||
8 | Rated closed circuit breaking current | A | 630 | |||
9 | Rated active load breaking current | A | 630 | |||
10 | Rated cable charging breaking current | A | 10 | |||
11 | Rated transfer current | A | —— | 1700 | ||
12 | Expected short-circuit breaking current | KA | —— | 50 | ||
13 | Mechanical life | times | 2000 | |||
14 | SF6 gas rated inflation pressure (20ºC gauge pressure) | MPa | 0.04 | |||
15 | SF6 gas highest pressure (20ºC gauge pressure) | MPa | 0.045 | |||
16 | Annual air leakage rate | %/Y | 0.5 | |||
17 | Synchronicity of opening and closing | ms | ≤3 | |||
18 | circuit resistance | μΩ | ≤100 |