Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
15kV Indoor SF6 Switch-Disconnector FL(R)N36 Load Break Switch (LBS) is a rotary load switch using SF6 gas for insulation and arc extinguishing, designed for 15kV power distribution systems. Each unit is sealed with 0.4bar SF6 gas and can be installed vertically or horizontally. A common installation in ring main units involves a horizontal steel partition between the cable and busbar rooms, ensuring safety during operation and maintenance.
Combining the FLN36-15 indoor high-voltage SF6 load switch with other electrical components allows for control and protection functions, ideal for industrial and mining enterprises, civil power supply, and secondary substations. The FLRN36-15kV load switch-fuse combination is particularly suited for ring network power supply units, matching transformer protection characteristics.
No. |
Items |
Unit |
Value | |||||
FLN36-15 | FLRN36-15 | |||||||
1 | Rated voltage | KV | 15 | |||||
2 | Rated frequency | Hz | 50/60 | |||||
3 | Rated current | A | 630 | 1250 | ||||
4 | Rated insulation level |
1 min power frequency withstand voltage |
phase-to-phase | KV | 42 | |||
phase-to-earth | KV | 42 | ||||||
fracture | 48 | |||||||
Lightning impulse withstand voltage voltage(peak) |
phase-to-phase | 75 | ||||||
phase to earth | 75 | |||||||
fracture | 85 | |||||||
5 | Auxiliary circuit 1 min power frequency | V | 2000 | |||||
6 | Rated thermal stability current /duration (3s/2s) | main switch | KA | 20/3 | ||||
earthing switch | 20/2 | |||||||
7 | Rated short-circuit making current | KA | 50 | 50 | ||||
8 | Rated closed circuit breaking current | A | 630 | |||||
9 | Rated active load breaking current | A | 630 | |||||
10 | Rated cable charging breaking current | A | 10 | |||||
12 | Rated transfer current | A | -- | 1500 | ||||
13 | Expected short-circuit breaking current | KA | 20 | 20 | ||||
14 | Mechanical life | times | 2000 | |||||
15 | SF6 gas rated inflation pressure (20ºC gauge pressure) | MPa | 0.04 | |||||
16 | SF6 gas highest pressure (20ºC gauge pressure) | MPa | 0.045 | |||||
17 | Annual air leakage rate | %/Y | 0.5 | |||||
18 | Synchronicity of opening and closing | ms | ≤3 | |||||
17 | circuit resistance | μΩ | ≤100 | |||||
Fuse Rated Parameters | ||||||||
No. |
Rated Voltage (KV) |
Fuse Rated Current (A) |
Fuse Link Rated Curent(A) |
Rated Breaking Current (KA) |
||||
1 | 12 | 40 | 6.3,10,16,20,25,31.5,40 | 40 | ||||
2 | 100 | 506,380,100 | 40 | |||||
3 | 125 | 125 | 50 |