Product Description
V12D/630/20X features easy installaton, low maintenance, extended service lfe,compact design, cost- effectiveness, and high safety reliabilityThis product complies with GB/T 1984-2024 "High-voltage alternating-current circuit-breakers"Main Circuit Parameters: Rated current. 630A; $hort-circuit breaking capacity. 20kA (4s) and 25kA (3s); Mechanical endurance: 10,000 operations.Grounding Circuit Parameters: Short-circuit breaking capacity: 20kA (2s); Mechanical endurance: 3,000 operations.
Product Parameters
Main technical parameters
No. |
Item |
Unit |
Technical Parameters |
1 |
Rated Frequency |
Hz |
50 |
2 |
Rated Current |
A |
630 |
3 |
Rated Short-Time Withstand Current |
kA |
20/25 |
4 |
Rated Peak Withstand Current |
kA |
50/63 |
5 |
Rated Short-Circuit Duration |
s |
4 |
6 |
Rated Short-Circuit Making Current |
kA |
50 |
7 |
Rated Operating Sequence |
- |
O-0.3s-CO-180s-CO |
Mechnical parameters
No. |
Item |
Unit |
Technical Parameters |
1 |
Main Circuit Resistance |
μΩ |
45 |
2 |
Overtravel |
mm |
2-3 |
3 |
Contact Gap |
mm |
8-10 |
4 |
Contact Bounce |
ms |
≤ 2 |
5 |
Average Opening Speed |
m/s |
1.0-1.4 |
6 |
Average Closing Speed |
m/s |
0.6-1.1 |
7 |
Three-phase Opening Asynchronism |
ms |
≤ 2 |
8 |
Three-phase Closing Asynchronism |
ms |
≤ 2 |
Installation Instructions

Company Profile




FAQ
Q 1. Are you factory?
A.YES, Welcome to visit our company and factory.
Q 2. How's the delivery time?
A. Usually it will take about 7-30 days for MOQ
Q 3.Can you design customer's packing?
A.YES.We can customized the package for you.
Q 4.Do you have abilityfor OEM/0DM cooperation?
A.OEM/ODM cooperation is welcomed. And we have full experience about them.
Q 5.We wants to know month capacity.
A. lt depends on which model. Generally, month capacity can reach near 100,000pcs.